G2000N Series Gas Detector

The G2000N is used in combination with the Model GM600 universal display unit and the Model Ultra TGX transmitter series for toxic gas detection, combustible gas detection, infrared hydrocarbon gas detection and organic compound gas detection

oem/odm
G2000N Series Gas Detector
G2000N Series Gas Detector
G2000N Series Gas Detector
G2000N Series Gas Detector
Application:

toxic gas, combustible gas, infrared hydrocarbon gas, organic compound gas.

Description Technical Data Download Application Contact us Related Products

Description

The gas concentration readings on the Model GM600 Universal Display Unit are displayed in LCD formats such as % vol,% LEL, ppm, ppb, and mg/m³. The display unit processes output signals from the Model Ultra TGX series, which correspond to detected gas concentrations. The GM600 connects to sensors via signals from the Ultra TGX series, specifying the gas type and operational range of each sensor. The GM600 standard output configuration includes high-level alarms, low-level alarms, auxiliary alarms, and fault relays. It features isolated/non-isolated 0-20 mA output models with optional HART communication, dual redundant MODBUS communication channels, and Bluetooth or wireless connectivity via dedicated mini-programs for rapid setup and diagnostics. Designed for continuous monitoring of toxic gas concentrations in production environments across oil and chemical industries, this equipment serves as an ideal solution for protecting personnel and facility safety.

 

Advantage

● Bluetooth and wireless technology allow mobile devices to be configured and calibrated through dedicated small programs, with an intuitive human-computer interface.

● UltraSen® proprietary technology, using intelligent algorithms to automatically adapt to the field environment, thereby compensating for sensors, suppressing zero drift and sensitivity loss, and extending sensor life.

● The sensor has an internal ID chip, and there are independent algorithm parameters for each sensor to ensure the consistency of sensor performance.

● The optional wireless interconnection module can network the independent gas detector to determine the gas leakage point more accurately.

● Display units, gas transmitters and mobile devices can be automatically interconnected Product Advantages without additional operation.

Technical Data

Detection gas Combustible gas, toxic gas, oxygen
Sensor type Catalytic combustion; Electrochemical; Infrared; PID
Input power Rated 24VDC, 20-36VDC/250mA (Max) (typical value 190mA)
Accuracy

± 5%FS toxic gas

±2%FS or ±0.5%V/V oxygen

±3%LEL(<50%LEL); ±5%LEL(>50%LEL)Catalytic

Drift ≤±5%FS/Year
Repetitiveness ≤2%
Response time Combustible gas T90: ≤20s;CO T90: ≤15s;O2 T90: ≤15s;H2S T90: ≤25s
Cable size 1000m(Max):RVVP3x1.5mm2
Explosion-proof grade Ex db ib IIC T5/T6 Gb: Ex tD IIC T85℃ Db
Protection level IP66
Temperature -40℃~+70℃(Except for the sensor);-55℃~+85℃(Except for the sensor)
Humidity 0~95%RH,no condensation
Shell materials 316 stainless steel/aluminum alloy
Size 250mm*130mm*140mm(L*W*H);
Electrical interface 5xM25(optional);5x3/4"NPT(optional)
Power consumption 24VDC@150mA (3.6W) MAX;Heating24VDC@300mA(7.2W)MAX
Signal output 4-20mA;HART7(optional);4 relay; dual MODBUS
Relay capacity 6A@250VAC,5A@24VDC
Weight 3.05Kg stainless steel; 1.25Kg aluminum alloy
Warranty 2 years (excluding sensors)

Application

Oil-and-Gas-drilling

Oil and Gas drilling

Metallurgy

Metallurgy

Mining-industry

Mining industry

Power-Plant

Power Plant

Steel-plant

Steel plant

Gas-pipeline-project

Gas pipeline project

Contact us

We will reply to your message as soon as possible.

    • *

    • *

    • *

    PassWord